Jumper Offsets

Jumper Offsets

A jumper offset in a plumbing system uses a combination of fittings to go around an obstacle, such as a cylindrical tank. Using simple math and a few constants, it’s possible to find the center-to-center lengths for each pipe in the offset, which are outlined below. To find the missing values in a jumper offset you will need to remember the constants for right triangles used in a 45 degree offset; which are:

To find the hypotenuse (the long side) multiple a short
side by 1.414
To find a short side when the hypotenuse is known, multiply it by 0.707

Jumper offset using 45-90-45 fittings

0a9467e57804b75a0bc2be038a3cc581

 

 

Use the image above to sketch out the jumper offset using the variables below. After a couple practice runs, try changing the numbers. R – 4″ A = 3″ E = 2″ C – 20″
Step 1 – The first thing you need to find is the side of the secondary square (G). So add (R) + (A) = (G)4 + 3 = 7″ This number is known as the secondary square (G).

Step 2 – Multiplying the secondary square by 2 will give you the length of pipe (B), and the length of pipe (F) to the center line of the tank. (G) x 2 = (B) so to find the end to end length of pipe (B) which ends on the center line it would be 7″ x 2 = 14″.

Step 3 – To find the length of pipe (F) will require two steps, first you have to multiply dimension (E) by 1.414 to find the length of pipe (F) below the center line of the tank, then add that number to result you got in step two above. 2″ x 1.414 = 2.828 then 2.828″ + 14″ = 16.828″ or roughly 16 7/8″

Step 4 – To find (H) also known as the offset, multiply the diagonal (B) by the constant 0.707 (H) = 14 x 0.707 = 9.898″

Step 5 – Find dimension (J) by adding the offset (H) with (E) (H) +(E) = (J) / 9.898 + 2 = 11.898″

Step 6 – Finding the length of pipe (D) is simple subtraction. (C) – (j) = (D)20 – 11.898 = 8.102″